A Two-Layer Control Strategy for the Participation of Energy Storage Battery Systems in Grid Frequency Regulation

Pan Zhang,Shijin Xin,Yunwen Wang,Qing Xu,Chunsheng Chen,Wei Chen,Haiying Dong
DOI: https://doi.org/10.3390/en17030664
IF: 3.2
2024-01-31
Energies
Abstract:A two-layer control strategy for the participation of multiple battery energy storage systems in the secondary frequency regulation of the grid is proposed to address the frequency fluctuation problem caused by the power dynamic imbalance between the power system and load when a large number of new energy sources are connected to the grid. A comprehensive allocation model based on area regulation requirement (ARR) signals and area control error (ACE) signals is proposed to obtain the total output of the secondary frequency modulation (FM) demand with a higher degree of adaptation when the FM units respond to the automatic generation control command, and the total output is reasonably allocated to each FM unit by using the two-layer control. Considering the dynamic fluctuation of the grid frequency, the fluctuation is dynamically suppressed in real-time by applying model predictive control to successfully forecast the frequency deviation while realizing the deviation-free correction in the frequency dynamic correction layer. The optimal power distribution of FM units based on the distributed control concept, as well as the power depth of each unit, are coordinated in the equalization control layer while keeping a decent battery charge level. Finally, in Matlab/Simulink, the proposed control approach is simulated and validated. The findings show that the suggested control approach can suppress frequency difference fluctuation, keep the battery charged, and reduce the unit's FM loss.
energy & fuels
What problem does this paper attempt to address?
The main problem that this paper attempts to solve is the frequency fluctuation problem caused by the large - scale integration of new energy sources into the power grid. Specifically, when a large amount of new energy (such as wind energy, solar energy, etc.) is connected to the power grid, due to the instability of these energy sources, the power dynamic imbalance of the power system will be caused, which in turn will lead to the grid frequency fluctuation. Traditional frequency regulation units are unable to cope with this rapidly changing demand. Therefore, this research proposes a two - layer control strategy, aiming to solve this problem by involving multiple battery energy storage systems (BESS) in the secondary frequency regulation of the power grid. ### Main contributions of the paper 1. **Proposing a two - layer control strategy**: This strategy can more efficiently use multiple BESS to participate in the secondary frequency regulation of the power grid. By reasonably allocating the frequency regulation requirements, it improves the adaptability and accuracy of frequency regulation. 2. **Comprehensive allocation model**: Based on the area regulation requirement (ARR) signal and the area control error (ACE) signal, a comprehensive allocation model is proposed to obtain a higher fitness, ensuring that the total output of the frequency regulation unit is more reasonable when responding to the automatic generation control (AGC) command. 3. **Real - time dynamic suppression of frequency fluctuations**: By applying model predictive control (MPC), this strategy can predict and correct frequency deviations in real - time under the dynamically changing grid frequency, achieving non - differential regulation. 4. **Optimizing power allocation**: In the balanced control layer, based on the concept of distributed control, the optimal power allocation of each frequency regulation unit is coordinated, while maintaining an appropriate charging level of the battery, reducing the frequency regulation loss. ### Formula presentation 1. **Total output of secondary frequency regulation requirements based on ACE signal**: \[ \Delta P_{\text{AGC}, i}(s)=\frac{\text{ACE}_i(s)K_I}{s}=-B_i\left[\sum_{j = 1}^{J}\Delta P_{Bj}(s)G_{Bj}(s)+\Delta P_G(s)G_g(s)-\Delta P_{Li}(s)\right]\frac{K_I}{M_is + D_i+K_IG_g(s)+\Delta P_{\text{tie}, i}(s)} \] 2. **Total output of secondary frequency regulation requirements based on ARR signal**: \[ \Delta P_{\text{AGC}, i}(s)=\text{ARR}_i(s)=-B_i\left[\sum_{j = 1}^{J}\Delta P_{Bj}(s)G_{Bj}(s)+\Delta P_G(s)G_g(s)-\Delta P_{Li}(s)\right]\frac{K_I}{M_is + D_i+K_IG_g(s)+\Delta P_{\text{tie}, i}(s)} \] 3. **Difference between ARR and ACE signals**: \[ \Delta A(s)=\text{ARR}_i(s)-\text{ACE}_i(s) \] ### Conclusion This paper effectively solves the frequency fluctuation problem caused by the large - scale integration of new energy sources into the power grid by proposing a two - layer control strategy. This strategy not only improves the adaptability and accuracy of frequency regulation, but also ensures the long - term stable operation of the battery energy storage system by optimizing power allocation and real - time dynamic suppression of frequency fluctuations.