Micro-extraction method for the analysis of flame retardants in dust collected from air filters from HVAC systems

Morgan L Schachterle,Luis E Lowe,Christopher R Butler,Allen M Schoffstall,Janel E Owens
DOI: https://doi.org/10.1016/j.mex.2024.102693
2024-04-08
MethodsX
Abstract:Dust is a sink for many semi-volatile compounds including flame retardants of the organophosphate ester (OPE) and brominated flame-retardant (BFR) classes. Given the large amount of time that we spend indoors, our exposure to these compounds via dust is of significant interest. Here, we present a novel microextraction approach to determine quantitative levels of selected OPEs and BFRs sampled from residential air filters from HVAC systems using a small volume of solvent. Dust samples (25 mg) is extracted with 1 mL of hexane/acetone (50/50, v/v). Upon solvent extraction of these HVAC dust samples, the analytes (TCPP, TDCPP, TPHP, T24DtBPP, TBBPA, and TriBBPA) were quantified via gas chromatography-mass spectrometry (GC/MS) or liquid chromatography-mass spectrometry (LC/MS). The methods for extracting these compounds from HVAC dust samples are detailed here with extensive method validation data to demonstrate accuracy and precision of these methods. •Dust is a sink for many semi-volatile compounds, including novel or emerging indoor pollutants like the organophosphate ester flame retardant T24DtBPP.•Here, a small amount of dust (25 mg) is extracted with a small volume of solvent (1 mL hexane and acetone) prior to analysis via chromatographic separation and mass spectrometric detection.
What problem does this paper attempt to address?