Comparison of three stability analysis methods for delayed cyber-physical power system

Weikang Gao,Hua Ye,Yutian Liu,Liang Wang,W. Ci
DOI: https://doi.org/10.1109/CICED.2016.7576361
2016-08-01
Abstract:The power system with wide-area damping controllers (WADC) embedded is essentially complex delayed cyber-physical power system (DCPPS) since time delays are introduced during transmitting and processing wide-area measurements. In this paper, three methods for stability analysis of DCPPS, i.e., delay-dependent stability criterion in the time domain, Padé approximation-based method as well as explicit infinitesimal generator discretization-based method (EIGD) in the frequency domain are extensively compared from both theoretical and numerical analysis in terms of conservativeness, accuracy, scalability and the capability of handling multiple delays. Simulation results reveals that: (1) The conservativeness in delay margin derived by delay-dependent stability criterion reaches to 7.09% for the two-area four-machine test system. (2) Padé approximation-based eigen-analysis method is sufficiently accurate even a low order of the approximation, e.g., 3rd order, is used. (3) Padé approximation-based eigen-analysis method is more efficient than EIGD for small stability analysis of large DCPPS.
What problem does this paper attempt to address?