Abstract:Renewable energy generation technologies, heat pumps or electric vehicle (EV) charging stations use active power electronics such as IGBT or MOSFET for AC to DC conversion with the consequence of emissions in the higher frequency range above 2 kHz (non-intentional supraharmonic emissions) and with an impact to the higher frequency grid impedance. In this study the impact of active power electronics on the higher frequency grid impedance in the range up to 150 kHz is analyzed. As existing grid modelling solutions do not consider these technologies sufficiently, this study analyzes the impact of a vehicle to grid (V2G) chargers to a representative distribution grid considering different grid topologies and different types of V2G chargers. The study shows that the additional capacitance and inductance (LCL filter, DC link capacitor) introduced in the electrical grid causes parallel and series resonances in a wide frequency range starting from 500 Hz up to 50 kHz. The grid topology and the number of V2G chargers connected determines the frequency range and characteristics of resonances. Finally, the major contribution of this study is outlining the importance of considering the higher frequency grid impedance for characterization of supraharmonic emissions (primary vs. secondary emissions) and their propagation.
energy & fuels,engineering, electrical & electronic
What problem does this paper attempt to address?