Thermodynamic analysis and optimization of a modified cascade refrigeration system using two-phase ejectors and low GWP fluids

Augusto Veiga de Souza,Paulo Eduardo Lopes Barbieri,Débora Carla Silva Mól,Raphael Nunes de Oliveira,Ralney Nogueira de Faria
DOI: https://doi.org/10.1016/j.ijrefrig.2024.02.003
IF: 4.14
2024-04-01
International Journal of Refrigeration
Abstract:This study optimizes a two-phase ejector cascade refrigeration system using a Particle Swarm Optimization (PSO) algorithm for low-temperature applications. The constant area analysis method identifies ejector design parameters employing refrigerants with low global warming potential (GWP), such as N H 3 , R 290 , R 1234 y f , and R 1234 z e ( E ) . The results indicate greater exergy destruction with the R 1234 y f – C O 2 pair, while the N H 3 – C O 2 pair presented the highest optimized Coefficient of Performance (COP), reaching 1.81. It is observed that an increase in ejector nozzle diameters occurs as cooling capacity increases, and nozzle efficiency also influences the variation in ejector nozzle areas and the ideal area ratio. The research demonstrates the potential of cascade cooling systems with ejectors, providing additional insights into ejector performance to achieve greater efficiency and sustainability in low-temperature applications.
engineering, mechanical,thermodynamics
What problem does this paper attempt to address?