Determining an optimal number of spares for hydro one 230/115 kv auto-transformers

G. Hamoud,P. Zhao
DOI: https://doi.org/10.1109/PESGM.2017.8274456
2017-07-01
Abstract:A reliability study has been performed recently at Hydro One to evaluate the optimal numbers of spare transformers required for 250 MVA and 125 MVA, 230/115 kv, 3 phase auto-transformers of the Hydro One's transmission system. In this study, a probabilistic method based on a Markov model and a bulk power reliability program was developed in determining the number of spare units for each group of auto-transformers. The purpose of this paper is to describe the assessment approach used in the study and to present the study findings and its recommendations.