Non-linear Control of the Power Injected Into a Weak Grid by a Self-Synchronized Inverter

Sebastian Gomez Jorge,Jorge A. Solsona,Claudio A. Busada,Leire C. Aguirre-Larrayoz,M. Itsaso Martínez,Gerardo Tapia-Otaegui
2024-10-10
Abstract:In this work, a non-linear controller designed using non-linear transformation linearization and feedback is proposed for an inverter connected to a weak grid through a single-stage inductive filter. The proposed strategy is self-synchronized, so that it is not necessary to have a voltage sensor at the Point of Common Coupling (PCC). The strategy allows to robustify, in the presence of a weak grid, a strategy that has already been demonstrated to allow a significant reduction in the size of the DC-link capacitor of the converter. For this purpose, a state observer is designed that allows estimating the voltage at the PCC from the measurement of the output inductor current. A start-up controller is also included, which allows synchronization even in the case of system start-up. Simulation results are presented for different operating cases, including start-up, normal operation, and grid-voltage sags and swells. In all these cases, it is considered that the exact parameters of the grid to which the inverter is connected are unknown.
Systems and Control
What problem does this paper attempt to address?