Abstract:The electric power transformer is a critical component in electrical distribution networks, and the diagnosis of faults in transformers is an important research area. Frequency Response Analysis (FRA) methods are widely used for analyzing winding faults in transformers, particularly in Chinese power stations. However, the current approach relies on manual expertise to interpret FRA curves, which can be both skill-intensive and lacks precision. This study presents a novel approach using a Multilayer perceptron model to directly model and analyze FRA data, simulating various winding fault types and degrees in 12-disc winding and 10-disc winding transformers with different connection configurations, resulting in three distinct datasets. Six different Multilayer perceptron architectures were developed, with optimal models achieving recognition accuracies of over 99.7% for diagnosing fault degrees and more than 90% for fault types. Hence, this paper has yielded a model architecture that exhibits commendable performance in diagnosing various fault types and their severities in different models of transformers when utilizing different FRA connection methods. Additionally, a specialized diagnostic system called FRA-DiagSys with two-stage model utilization was developed, achieving 100% accuracy in diagnosing fault types and degrees for a specific winding-10 power transformer, surpassing other diagnostic methods and strategies.
Computational Engineering, Finance, and Science
What problem does this paper attempt to address?
### What problem does this paper attempt to solve? This paper primarily aims to address the issue of fault diagnosis in power transformer windings. Specifically, it seeks to improve current fault diagnosis methods through the following points: 1. **Analysis of Existing Problems**: - The current Frequency Response Analysis (FRA) method relies on human experts to interpret FRA curves, which requires specialized knowledge and lacks precision. - The distribution of FRA curves varies across different models and operating conditions, and manual experience lacks quantitative representation, making knowledge transfer difficult. - Solely relying on manual curve analysis cannot achieve high accuracy in diagnosing different types of faults and their severity. 2. **Proposed New Method**: - The paper proposes a new method based on a Multi-Layer Perceptron (MLP) model to directly model and analyze FRA data. - This method can simulate various winding fault types and severities under different connection configurations for different transformer models (such as 12-disk and 10-disk windings) and generate three independent datasets. - The study developed six different MLP architectures, with the optimal model achieving over 99.7% recognition accuracy in diagnosing fault severity and over 90% recognition accuracy in diagnosing fault types. 3. **Development of Diagnostic System**: - A specialized diagnostic system named FRA-DiagSys was developed, employing a two-stage model utilization method, achieving 100% diagnostic accuracy on a specific model (10-disk winding transformer). - This system surpasses other diagnostic methods and strategies, demonstrating high accuracy and reliability in practical applications. Through these methods, the paper aims to provide a new, efficient, and automated fault diagnosis system for power transformer windings to replace traditional manual diagnostic methods.