On the damping of power systems during inverter-based blackstart

Adolfo Anta,Diego Cifelli
2024-05-26
Abstract:The massive deployment of inverter-based generation poses several challenges to system operators but also offers new opportunities. In the context of grid recovery, inverter-based generation is expected to take over new responsibilities, as conventional generation that are blackstart capable are being decommissioned. Inverter-based facilities, being very flexible and controllable, have the ability to contribute during grid restoration, although it is still unclear how to deal with the limited ratings of batteries, PV, etc. and how to address nonlinear effects such as inrush currents or harmonics. In this direction, the requirements of grid-forming inverters to comply with black start capabilities are still to be defined. During the first steps of a grid restoration process the dynamics of the grid largely vary from the grid behaviour under normal operation. In particular, the grid is nearly unloaded and therefore poorly damped. Indeed, overvoltages and resonances are a common concern during the energization of long transmission lines. In this work we analyse the spectral properties of unloaded transmission lines, and describe the impact of voltage controllers on the damping of the system. As a byproduct, this analysis can be leveraged to propose high level requirements for grid-forming devices, in order to provide adequate damping during the early stages of a grid restoration process.
Systems and Control
What problem does this paper attempt to address?
This paper mainly discusses the attenuation problem of the power system during the inverter-based grid restoration (black start) process. With the deployment of a large number of inverter generation facilities, they need to assume the role of traditional generator units in grid restoration. However, it is still unknown how to use these flexible and controllable facilities to handle the limited rated values of batteries, photovoltaics, and other devices, as well as nonlinear effects (such as inrush current or harmonics). The focus of the research is on the dynamic analysis of the early stages of grid restoration, particularly the electrical characteristics of unloaded transmission lines. The authors analyze the spectral characteristics of unloaded transmission lines and study the influence of voltage controllers on system attenuation. They propose an analysis framework that does not rely on numerical simulations but analyzes the impact of different control parameters on system damping by establishing a state space model and its relationship with Toeplitz matrices. In addition, they also explore how virtual resistor loops can help improve overall damping. The paper mentions that traditional grid restoration strategies usually adopt a divide-and-conquer approach, but this method may lead to synchronization issues between regions. A faster strategy is to define a backbone structure and supply power to it all at once, but this can also lead to low damping and resonance problems. In the absence of loads, inverters may need to disconnect all loads to start the grid, which is different from traditional power plants as they have larger rated values. The research found that voltage controllers, such as proportional controllers, may reduce system damping while tracking the reference voltage, but adding virtual resistor loops can improve damping. In conclusion, the paper suggests the need to develop advanced specifications for the black start function of inverters and emphasizes the importance of control design in terms of voltage amplitude dynamics. In summary, the paper aims to provide guidance for the control strategies of inverters by deepening the understanding of the dynamic characteristics of the early stages of grid restoration, in order to ensure a more efficient grid restoration process.