Microgrid Pre-Synchronization Scheme for Suppressing Voltage Fluctuations and Avoiding Frequency Out-of-Limits

Renxi Gong,Yan Qin,Tao Liu,Jiawei Xu,Zhihuan Wei
DOI: https://doi.org/10.3390/electronics13020428
IF: 2.9
2024-01-20
Electronics
Abstract:Pre-synchronization control is needed when the microgrid changes from an off-grid state to a grid-connected state. Aiming to resolve the problems of frequency overstep and voltage fluctuation in traditional pre-synchronous grid-connection schemes, a micro-grid pre-synchronous grid-connection scheme is proposed that can solve both frequency overstep and voltage fluctuation at the same time. Firstly, the feedforward disturbance compensation V/f control strategy of the load voltage and current is introduced to the energy storage system to suppress voltage fluctuations caused by power changes. Then, the V/f control strategy of the energy storage system is improved to suppress voltage fluctuations caused by frequency fluctuations when the starting phase of pre-synchronization is enacted. Finally, PI parameters are optimized based on the golden jackal optimization algorithm to meet the requirements of frequency fluctuation and grid-connection speed in the pre-synchronization process. A large number of simulation experiments demonstrate the effectiveness of the proposed method.
engineering, electrical & electronic,computer science, information systems,physics, applied
What problem does this paper attempt to address?
### Problems the Paper Attempts to Solve This paper aims to address the issues of voltage fluctuations and frequency limit violations that occur during the transition of a microgrid from island mode to grid-connected mode. Specifically: 1. **Voltage Fluctuations**: Traditional pre-synchronization schemes cannot effectively suppress voltage fluctuations caused by changes in photovoltaic output during the grid connection process of an islanded microgrid. 2. **Frequency Limit Violations**: During the pre-synchronization adjustment process, traditional frequency control methods may lead to frequency exceeding the specified range, thereby affecting the safe and stable operation of the equipment. To solve these problems, the paper proposes a new pre-synchronization grid connection scheme. This scheme improves the V/f control strategy, introduces feedforward disturbance compensation, and differential components to enhance the damping effect of frequency control. Additionally, it utilizes the Golden Jackal Optimization (GJO) algorithm to optimize PI parameters, meeting the requirements for grid connection speed and frequency fluctuations. Extensive simulation experiments have verified the effectiveness of this method.