Fault direction estimation in radial distribution system using phase-change in sequencecurrent

Ashok Kumar Pradhan,A. Routray,S. M. Gudipalli
DOI: https://doi.org/10.1109/TPWRD.2007.905340
2007-10-01
Abstract:Summary form only given. This paper presents a method for estimating the direction of fault in such radial distribution systems using phase-change in current. The difference in phase angle between the positive sequence component of current during fault and prefault conditions has been found to be a good indicator of the fault direction in a three phase system. A rule base formed for the purpose decides the location of fault with respect to the relay in a distribution system. Such a strategy reduces the cost of voltage sensor and/or connection for a protection scheme which is of relevance in emerging distributed generation (DG) systems. The algorithm has been tested through simulation for different radial distribution systems.
What problem does this paper attempt to address?