Abstract:In this paper, a hybrid measurement- and model-based method is proposed which can estimate the dynamic state Jacobian matrix and the dynamic system state matrix in near real-time utilizing statistical properties extracted from PMU measurements. The proposed method can be used to detect and identify network topology changes that have not been reflected in an assumed network model. Additionally, an application of the estimated system state matrix in online dynamic stability monitoring is presented.
What problem does this paper attempt to address?
The problem that this paper attempts to solve is to use PMU (Phasor Measurement Units) measurement data to estimate the dynamic state Jacobian matrix and the dynamic system state matrix in real - time in the power system. Specifically, the paper proposes a method that combines measurement and model, which can use the statistical characteristics extracted from PMU measurement data to estimate these matrices under near - real - time conditions. The main purposes of this method are:
1. **Detect network topology changes**: By comparing the dynamic state Jacobian matrix calculated based on the assumed network model with the matrix estimated from the actual measurement data, topology changes that are not reflected in the network model can be identified.
2. **Online dynamic stability monitoring**: Using the estimated system state matrix, online dynamic stability monitoring can be carried out, such as estimating the critical eigenvalues of the system, so as to evaluate the degree of the system approaching instability.
3. **Parameter estimation**: In addition to estimating the Jacobian matrix and the system state matrix, the paper also proposes a method to estimate the damping coefficient of the generator, which requires the known network model, the generator electromotive force and the variance of load changes.
### Main contributions
- **No need for a complete network model**: The method proposed in the paper does not require a complete network model (topology and parameters) when estimating the Jacobian matrix, only the inertia constant \(M\) of the generator needs to be known.
- **Near - real - time estimation**: This method can use PMU data for estimation under near - real - time conditions, which is suitable for online monitoring and control.
- **Wide application**: The estimated system state matrix can be used for a variety of applications, such as model verification, online stability monitoring, oscillation analysis and control, etc.
### Method overview
The paper proposes a method that combines measurement and model. The main steps are as follows:
1. **Data collection**: Use PMU installed on all generator buses to collect measurement data of voltage and angle.
2. **Covariance matrix calculation**: Calculate the sample covariance matrices \(Q_{\delta\delta}\) and \(Q_{\omega\omega}\) of rotor angle \(\delta\) and rotor speed \(\omega\) from PMU data.
3. **Jacobian matrix estimation**: Use the formula \(\frac{\partial P_e}{\partial \delta}=M Q_{\omega\omega}Q_{\delta\delta}^{-1}\) to estimate the Jacobian matrix.
4. **System state matrix estimation**: If the damping coefficient \(D\) of the generator is known, the system state matrix \(A\) can be constructed.
5. **Damping coefficient estimation**: If the damping coefficient \(D\) is unknown or uncertain, it can be estimated through additional steps, but this requires the known network model, the generator electromotive force and the variance of load changes.
### Case studies
The paper verifies the effectiveness of the method through three case studies:
1. **Standard WSCC 3 - generator 9 - node system**: It shows how to use this method to detect network topology changes.
2. **IEEE 39 - node 10 - generator system**: It not only verifies the estimation accuracy of the Jacobian matrix, but also shows how to identify the location of topology changes.
3. **The situation with some missing PMU data**: Even if some PMU data are missing, this method can still estimate part of the Jacobian matrix and be used to detect and locate topology changes.
In conclusion, the paper proposes an innovative method to estimate the dynamic state matrix of the power system using PMU data and statistical characteristics under near - real - time conditions, which has important theoretical and practical application values.