Impedance Network Model Based Modal Observability and Controllability Analysis for Renewable Integrated Power Systems

Ying Zhan,Xiaorong Xie,Yang Wang
DOI: https://doi.org/10.1109/tpwrd.2020.3018149
IF: 4.825
2021-08-01
IEEE Transactions on Power Delivery
Abstract:The complex interactions between renewables and AC/DC networks have brought new oscillation issues. To effectively monitor and suppress these oscillations, the observability and controllability of the oscillatory modes at different locations of the system must be investigated. To achieve this, the paper first defines the concept of modal observability and controllability using the responses of unit-pulse perturbations. Then an eigenvalue-decomposition based method is proposed to calculate these two indexes with the impedance network model (INM) as the input. The obtained modal observability(controllability) has many important applications and one of them is to facilitate the aggregation of the INM. The paper investigates this application by selecting an optimal aggregation port to ensure that the aggregated impedance can reflect the complete system dynamics. Finally, the proposed method is verified on a simple passive circuit and a practical wind power system that experienced actual subsynchronous resonance incidents. Theoretical results as well as EMT simulations demonstrate the effectiveness of the method.
engineering, electrical & electronic
What problem does this paper attempt to address?
The paper attempts to address the new oscillation problems in modern power systems caused by the complex interactions between renewable energy sources and AC/DC networks. Specifically: 1. **Background of the Oscillation Problem**: With the surge in the number of renewable energy sources, the dynamic behavior of modern power systems has significantly changed, leading to various oscillation problems. For example, wind turbines may interact with series compensation or weak grids, triggering sub-synchronous oscillations; interactions between different renewable energy sources may lead to high-frequency oscillations. These emerging oscillation problems affect power quality, jeopardize equipment safety, and threaten system stability, thus becoming a major concern for the integration of renewable energy. 2. **System Characteristics**: Actual large-scale renewable energy integrated power systems usually have the following characteristics: - Geographically widespread renewable energy sources with different controller configurations/parameters. - The system may be equipped with other power electronic devices, such as High Voltage Direct Current (HVDC) systems and Flexible AC Transmission Systems (FACTS). - The system topology may be complex, including meshed networks. 3. **Core of the Problem**: For such systems, the oscillation problems that occur usually involve multiple components, and the oscillation energy can spread over a large area. To effectively monitor and control these oscillations, it is crucial to understand the distribution of oscillation currents and the role of each component in forming the oscillations. Therefore, studying the observability and controllability of oscillation modes at different locations becomes very important. 4. **Limitations of Existing Methods**: Existing research methods include time-domain modal analysis methods and resonance modal analysis methods, but these methods have certain limitations, such as the impact of matrix non-regularity on calculation accuracy and their applicability only to steady-state resonance phenomena. 5. **Solution Proposed in the Paper**: This paper proposes a modal observability and controllability analysis method based on the Laplace domain Impedance Network Model (INM). By defining the concepts of modal observability and controllability and proposing a method based on eigenvalue decomposition to calculate these indices, the above problems are addressed. Additionally, the paper explores the application of this method in the aggregation of impedance network models, ensuring that the aggregated impedance can reflect the complete system dynamic characteristics by selecting the optimal aggregation ports. In summary, this paper aims to solve the complex oscillation problems caused by renewable energy in modern power systems by proposing a new modal observability and controllability analysis method, thereby improving system stability and safety.