A multi-objective approach for optimal placement of renewable energy sources, voltage regulators and capacitors in radial unbalanced distribution systems
Arubolu, Lavanya,Manyala, Ramalinga Raju
DOI: https://doi.org/10.1007/s00202-024-02388-7
IF: 1.63
2024-04-26
Electrical Engineering
Abstract:There are various challenges in integrating renewable energy sources (RES) into unbalanced distribution systems (UDS) due to the varying nature of loads and RES, as well as the degree of unbalance of the distribution systems. The challenges involved are modelling RES and loads and integrating these models into the complex power flow analysis of UDS. Most of the previous studies either focused on RES allocation in balanced distribution systems or RES allocation in UDS ignoring the varying nature of generation and load which could undermine or overestimate the potential benefits of RES allocation. Hence, in this work, a new approach for allocating photovoltaic and wind energy sources optimally in UDS considering varying nature of load and generation is proposed. The proposed approach employs pareto front-based multi-objective backtracking search algorithm (PMBSA) to get the best optimal size and location of RES by choosing minimisation of total real power loss (TPL), cumulative voltage deviation (CVD), voltage stability index (VSI) and total cost (TC) as objectives. Additionally, optimal allocation of automatic voltage regulators (AVR) and shunt capacitors is done in case there are any voltage limit violation problems. A probabilistic technique is employed to account for the time-varying nature of RES and load while solving optimal RES allocation problem. PMBSA is used in this work and interfaced with OpenDSS software to solve the UDS power flow problem. The proposed approach is implemented on IEEE 13-bus and 123-bus UDS, and the results indicate that, when PV and wind energy sources are optimally placed in a 123-node UDS, total cost, VSI index, power loss, and CVD reduce by 32.2%, 28.7%, 31.22%, and 4.5%, respectively, whereas when the traditional weighted sum approach is used for optimal allocation of RES, total cost, VSI index, power loss, and CVD reduce by 22.5%, 21.62%, 33.14%, and 3.33%, respectively, indicating the efficacy of the proposed approach.
engineering, electrical & electronic